Position: Home>PRODUCTS > GIS metal oxide arrester
Product introduction
Type designation | Rated Voltage | Continuous operating voltage | Min. reference voltage at D.C. 1mA | Steep current impulse residual voltage 1/10 μs | Lightning impulse residual voltage 8/20 μs | Switching impulse residual voltage 30/60 μs | 2ms rectangular current withstand | 4/10μs high current impulse withstand | Partial discharge |
kVr.m.s | kVr.m.s | kV | kVp | kVp | kVp | A | kA | pC | |
Y10WF-100/260 | 100 | 78 | 145 | 291 | 260 | 221 | 800 | 100 | 10 |
Y10WF-102/266 | 102 | 79.6 | 148 | 297 | 266 | 226 | 800 | 100 | 10 |
Y10WF-108/281 | 108 | 84 | 157 | 315 | 281 | 239 | 800 | 100 | 10 |
Y10WF-200/520 | 200 | 156 | 290 | 582 | 520 | 442 | 800 | 100 | 10 |
Y10WF-204/532 | 204 | 159 | 296 | 594 | 532 | 452 | 800 | 100 | 10 |
Y10WF-216/562 | 216 | 168.5 | 314 | 630 | 562 | 478 | 800 | 100 | 10 |