Position: Home>PRODUCTS > Metal oxide arrester > Three-phase combined arrester
Product introduction
Type designation | Rated Voltage | Connection mode | Continuous operating voltage | Min. reference voltage at D.C. 1mA | Steep current impulse residual voltage 1/10 μs | Lightning impulse residual voltage 8/20 μs | Switching impulse residual voltage 30/60 μs | 2ms rectangular current withstand |
kV | kV | kV | kV | kV | kV | A | ||
HY5WZ-5/13.5×5/13.5 | 5 | Phase to phase Phase to earth | 4.0 | 7.5 7.2 | 15.5 | 13.5 | 11.5 | 250 |
HY5WZ-10/27×10/27 | 10 | Phase to phase Phase to earth | 8.0 | 15.0 14.4 | 31.0 | 27.0 | 23.0 | 250 |
HY5WZ-17/45×17/45 | 17 | Phase to phase Phase to earth | 13.6 | 25.0 24.0 | 51.8 | 45.0 | 38.3 | 250 |
HY5WZ-51/150×51/134 | 51 | Phase to phase Phase to earth | 40.8 | 84.0 73.0 | 170.0 154.0 | 150.0 134.0 | 134.0 114.0 | 400 |
HY5WD-4/11.6×4/9.5 | 4 | Phase to phase Phase to earth | 3.5 | 7.0 5.7 | 13.0 10.7 | 11.6 9.5 | 9.4 7.6 | 400 |
HY5WD-8/23.3×8/18.7 | 8 | Phase to phase Phase to earth | 6.9 | 14.0 11.2 | 26.2 21.0 | 23.3 18.7 | 18.7 15.0 | 400 |
HY5WD-13.5/38.7×13.5/31 | 13.5 | Phase to phase Phase to earth | 10.5 | 23.2 18.6 | 43.3 34.7 | 38.7 31.0 | 31.0 25.0 | 400 |
HY2.5WD-4/11.6×4/9.5 | 4 | Phase to phase Phase to earth | 3.5 | 7.0 5.7 | 13.0 10.7 | 11.6 9.5 | 9.4 7.6 | 250 |
HY2.5WD-8/23.3×8/18.7 | 8 | Phase to phase Phase to earth | 6.9 | 14.0 11.2 | 26.2 21.0 | 23.3 18.7 | 18.7 15.0 | 250 |
HY2.5WD-13.5/38.7×13.5/31 | 13.5 | Phase to phase Phase to earth | 10.5 | 23.2 18.6 | 43.3 34.7 | 38.7 31.0 | 31.0 25.0 | 250 |